Ventiliatorius elektros spintai: kaip apskaičiuoti reikiamą oro srautą (m³/h)

Cabinet fan for electrical enclosures: how to calculate the required airflow (m³/h)

Frequency converters, power supplies, controllers and contactors give off heat. In a closed cabinet it builds up, and in summer the internal temperature can exceed what the equipment is rated for, causing faults whose cause is hard to find. A fan with a filter is the simplest solution, but it must be the right size. Here's how to calculate it.

Step 1. How much heat the equipment gives off

Add up the power losses (W) of the devices. They are listed in the manufacturers' datasheets (in English, power loss, heat dissipation). If losses are not stated, you can estimate them from the efficiency:

Losses = output power ÷ efficiency − output power

For example, a 24 V 10 A (240 W) power supply with 90% efficiency: 240 ÷ 0.9 − 240 ≈ 27 W of heat. The largest heat sources are usually frequency converters and power supplies.

Step 2. Permissible temperature difference ΔT

ΔT = maximum permissible temperature inside the cabinet − maximum ambient temperature. For example, if the inside must not exceed 35 °C and the workshop reaches up to 25 °C in summer, ΔT = 10 K.

Important: a fan only cools with ambient air. If the surrounding air is as warm as or warmer than the permissible temperature inside the cabinet, ventilation will not help – you need a heat exchanger or an air conditioner.

Step 3. Airflow formula

Formula used by Rittal and other manufacturers:

V = f × P ÷ ΔT

  • V – required airflow, m³/h;
  • P – heat losses in the cabinet, W;
  • ΔT – permissible temperature difference, K;
  • f – air property coefficient depending on altitude above sea level.
Altitude above sea level f, m³·K/(W·h)
0–100 m 3,1
100–250 m 3,2
250–500 m 3,3
500–750 m 3,4
750–1000 m 3,5

In Lithuania, f = 3.1–3.2 is sufficient almost everywhere.

Example: in the cabinet a frequency converter and power supplies, 400 W of losses in total, ΔT = 10 K, f = 3.1. V = 3.1 × 400 ÷ 10 = 124 m³/h.

Refinement: heat through the cabinet walls

When the cabinet is warmer than the surroundings, part of the heat escapes through the walls. It can be estimated with the formula Q = k × A × ΔT, where k is the heat transfer coefficient (about 5.5 W/m²K for a painted steel sheet) and A is the free surface area (not against a wall or another cabinet) in m².

Continuing the example: if the free surface is 1.5 m², about 5.5 × 1.5 × 10 ≈ 83 W escapes through the walls. The fan then has to handle 400 − 83 = 317 W, and V = 3.1 × 317 ÷ 10 ≈ 98 m³/h. If in doubt, calculate without the walls – you will get a safety margin.

Step 4. Filters reduce airflow – choose with a margin

A fan's catalogue airflow is often stated for free blowing. With an intake filter, an outlet grille and a clogged filter mat, the actual airflow is lower. Manufacturers' datasheets state airflows "with outlet filter" – select based on these and keep a margin. For the 98–124 m³/h example, it is worth looking at a ~250 m³/h model, e.g., Finder 7F.20.8.230.4250 (230 V AC, 250 m³/h, opening 224 mm), or at two smaller ones.

Fans with filter by airflow

Airflow Opening Example in the catalogue
24 m³/h 92×92 mm Finder 7F.20.8.230.1020, 230 V AC or 7F.20.9.024.1020, 24 V DC
55 m³/h 125×125 mm Finder 7F.20.8.230.2055, 230 V AC
85 m³/h – Schneider ClimaSys NSYCVF85M230PF, 230 V AC
100 m³/h 177×177 mm Finder 7F.20.8.230.3100, 230 V AC
250 m³/h 224×224 mm Finder 7F.20.8.230.4250, 230 V AC

Each fan also needs an outlet filter (grille) of the same opening size, e.g., Finder 7F.02.0.000.2000 (125 mm) ar Finder 7F.02.0.000.4000 (224 mm).

Installation and control

  • Location. The fan is usually mounted at the bottom of the cabinet and blows cool air inside, while the outlet filter sits at the top on the opposite side. Warm air rises, so the airflow passes through the whole cabinet. It is important that the air does not take a "short path" past the equipment.
  • Thermostat. To stop the fan running unnecessarily and the filter clogging faster, connect it via a thermostat with an NO contact (switches on as temperature rises), e.g., Finder 7T.81.0.000.2303 (0…60 °C). Thermostats with an NC contact are used to control heaters.
  • Filter mats replace regularly – a clogged filter greatly reduces airflow. Replacement mats: Schneider NSYCAF125, Rittal 3172.100.
  • IP rating. Once the fan is installed, it also determines the cabinet's protection rating. Most fans with filters are rated IP54. For more, see the article on IP protection ratings.