Emergency stop (E-STOP) button: requirements and correct wiring
The emergency stop button (E-STOP, "mushroom") is found on almost every machine, conveyor or line. It looks like a simple part, but it has strict requirements: the wrong button or incorrect wiring can mean the machine does not stop in a hazard. This article covers what the standards say, how to choose the button and how to wire it correctly.
Which standards apply
- EN ISO 13850 – design principles of the emergency stop function.
- EN 60204-1 – electrical equipment of machines: colours, stop categories, control circuits.
- EN 60947-5-5 – electrical emergency stop devices with mechanical latching (the button itself).
Important: emergency stop is an additional protective measure. It does not replace guards, interlocked guard doors or light curtains.
Requirements for the button itself
| Requirement | What it means in practice |
|---|---|
| Colour | A red actuator, with a yellow background (if any) behind it. That is why yellow labels are used, e.g. Schneider ZBY9320 (ø60 mm) ar Siemens 3SU1900-0BC31-0DA0 (ø75 mm). |
| Shape | Mushroom or palm-type head that can be easily pressed with the palm or fist. |
| Mechanical latching | A pressed button stays latched until a person deliberately releases it. |
| Contacts | NC (normally closed) with positive (direct) opening – the contact opens mechanically, even if it is welded. |
| Accessibility | At every workstation from which the machine may need to be stopped; unobstructed and visible. |
A button without latching (e.g. a simple red mushroom) and a green mushroom are not emergency stop devices, even if they look similar.
Release methods
- Turn to release – the most common, e.g. Schneider XB5AS8442 (1 NC), XB4BS8442 (metal, 1 NC), Eaton M22-PVT.
- Pull to release – Schneider XB5AT842, Eaton M22-PV.
- Key release – when only a responsible person may release it: Eaton M22-PVS.
The standard cut-out for mounting buttons in a panel cover is 22 mm (22.5 mm). If the button must be on the machine rather than on a panel, a ready-made pendant station is convenient, e.g. Schneider XALK178.
Stop categories
According to EN 60204-1, emergency stop must act as stop category 0 or stop category 1 stop:
- Category 0 – power to the drives is cut immediately (uncontrolled stop).
- Category 1 – the machine is stopped in a controlled way (e.g. a frequency converter brakes the motor), and only then is power cut.
Category 2 (stopped, but power is maintained) is not suitable for emergency stop. Which category to apply is determined by the machine's risk assessment.
Correct wiring
- Use NC contacts, connected in series in the safety circuit. If a wire breaks or a connector comes loose, the circuit opens and the machine stops – this is the safe state.
- Connect via a safety relay or safety controller, not just to a standard PLC input. A safety relay (e.g. Omron G9SA-301) monitors the circuit and controls contactors that cut power to the drives.
- Dual-channel wiring – where a higher safety level is required, use a button with 2 NC contacts (e.g. XB5AS8444 ar XB4BS8444), each contact going to a separate safety relay channel. This detects a single-channel fault.
- Contactor status monitoring – auxiliary NC contacts of the contactors are fed into the safety relay's feedback circuit, so the relay will not allow a restart if a contactor is welded.
- Separate reset Releasing the button must not restart the machine by itself. A separate reset action is required, followed by the normal start command.
- All buttons in one circuit. If the machine has several E-STOPs, any one of them must stop all hazardous parts covered by that zone.
The required safety level (PL according to EN ISO 13849-1) and whether a single channel is sufficient are determined by the risk assessment. Safety circuit work must be carried out by a qualified electrician.
Common mistakes
- an NO contact is used – if a wire breaks, the button stops working and nobody notices;
- the E-STOP is connected only to a PLC input, and stopping is done by the program;
- the machine restarts by itself when the button is released;
- the button is blocked, too far away or without a yellow background;
- never checked – the button's operation should be tested regularly (press it and make sure the machine stops and does not restart without a reset).
How to find them on inteq.lt
You can find emergency stop buttons, heads and yellow labels in the category Buttons and switches, safety relays and contactors – Relays and contactors. If you are replacing an old button, enter its code in search by code or upload a 📷 photo – we will select an equivalent. Can't find it? Write to us via užklausos formą.